Process 6 SIL VerificationAfter the safety system has been designed and each safety function configured, but before any safety functions are implemented, the performance requirements of each safety function must be verified against the requirements as documented in the Safety Requirement Specification.

For process safety applications this involves splitting a safety function into three subsystems – the sensor subsystem, the logic solver subsystem, and the final element subsystem. Each subsystem is then evaluated using the undetected failure mode and failure rate data for the subsystem components, the proof test interval, the diagnostic coverage factor, and the common cause (Beta) factor (if required). What results is a value for the average probability of a dangerous failure (PFDavg) which is directly related to the Safety Integrity Level (SIL); and the determination whether the architectural constraints for a particular SIL have been met, based on the hardware fault tolerance (redundancy) and safe failure fraction (diagnostic coverage).

FSE Global consultants have the necessary experience to take what is a relatively complex process and use certified safety performance modelling tools to provide an independent probabilistic safety and reliability analysis of each safety function; and deliver a comprehensive report detailing every aspect of the analysis.

We use cookies

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.